Viewer Changes In One View Are Not Seen The Other View With Switch Sheet Open

(Doc ID 2352113.1)

Last updated on FEBRUARY 14, 2018

Applies to:

Oracle Utilities Network Management System - Version 1.12.0.3 to 2.3.0.1.0 [Release 1.12 to 2.3]
Oracle Network Management for Utilities - DMS - Version 1.12.0.3 to 2.3.0.1.0 [Release 1.12 to 2.3]
Information in this document applies to any platform.

Symptoms

When a viewer is linked to a switch plan or a safety document, actions such as device operations and tagging in a detail view are not seen in the geographic view and vice versa. You have attached two examples of this behavior. Toggling the viewer between study and real time syncronizes the two views.

Steps to Reproduce:

1. Create a planned OTO and record a step to open the 11-M8 in the detail view. The 11-M8 circuit breaker will show open and the down stream conductor is off potential
2. Select the getaway point for the 11-M8 and object focus
The conductor in the geographic view is energized. but its expected to show de-energised on geo-graphic map also.

You are able re-produce this problem in QA environment 2.3.0.1