Trace Not Working For Phase Selected, Its Including All Phases

(Doc ID 2394087.1)

Last updated on MAY 02, 2018

Applies to:

Oracle Utilities Network Management System - Version 1.12.0.3 to 2.3.0.2.0 [Release 1.12 to 2.3]
Oracle Network Management for Utilities - DMS - Version 1.12.0.3 to 2.3.0.1.0 [Release 1.12 to 2.3]
Information in this document applies to any platform.

Symptoms

On : 2.3.0.0.0 version, Web Workspace

Tracing by phase does not work. After selecting an individual phase, the trace does a 3-phase trace and switches the phase buttons to All. This trace by phase function is important for diagnosing model problems.
 
Steps to Reproduce
 
1. Open a Viewer and set to View by Phases
 
2. Load the Viewer with circuitry that has single phase conductors.
 
3. From a 3-phase device, trace "all connected", "all direcdtions", B-phase only
 
The Trace is incorrectly done for all 3 phases and the trace phase button changes from B to All.

The correct behavior is:  the red and white phases are left out of the blue phase trace.
 