Symptoms

On : 2.4.0.0.0 version, Y-Delta-Y transformer with buried delta support in the new PF Engine

If a project has Y-Delta-Y transformers with 0 and 180 degrees phase shift between Y windings and delta winding is buried. Power flow results are OK for these transformers but the single phase to ground fault currents are not correct due to the missing buried delta winding, impedance not being considered in fault calculations. Need to add the winding support in the new power flow engine