Connection Attribute in PF_SOURCES is Wrongly Translated in PFService When Value is 0
(Doc ID 3061202.1)
Last updated on DECEMBER 10, 2024
Applies to:
Oracle Utilities Network Management System - Version 2.6.0.1.0 to 2.6.0.2.0 [Release 2.6]Oracle Network Management for Utilities - DMS - Version 2.6.0.1.0 to 2.6.0.2.0 [Release 2.6]
Information in this document applies to any platform.
Symptoms
On : 2.6.0.1.0 version, NMS PFService
Connection attribute in PF_SOURCES is wrongly translated in PFService when set to 0.
See several substations in Model Error state with Error of ConnectionType set to -1.
For example:
Information for object 299.16001, session 0
Device is a Gen
Device is a Node
Node=299.16001 | eeee | Branches->448.24101
Node Attributes:
Nominal kV = 115
isWye = 1
equivNetwork = 0
Solution Mode = SM_PF(1)
NodeState Attributes:
Voltages: A =(0,0), B =(0,0), C =(0,0), N =(0,0)
Gen Attributes:
substationName = <sub name>, connType = UNKNOWN(-1), controlType = GT_SLACK(0)
Checked the PFSources table and it looks like for this, the value is set to 0 not -1.
The connection type for the source:
- 0: wye (or star)
- 1: grounded wye (or star)
Cause