Exacheck Reports Topology Errors On Infiniband Network
(Doc ID 1483604.1)
Last updated on SEPTEMBER 28, 2021
Applies to:
Exadata Database Machine X2-2 Hardware - Version All Versions and laterInformation in this document applies to any platform.
Symptoms
Exacheck Reports some infiniband topology errors.
verify-topology also reports errors as seen below.
Leaf Switch <IB-SWITCH NAME>.<DOMAINNAME>.com with GUID 0x2128469d62a0a0has fewer than 8 links to compute nodes
It has 5 links (14A 13A 13B 12B 5A) to compute nodes
[ERROR]
However an investigation using listlinkup output and ibnetdiscover does not show any cable connectivity issues.
ibnetdiscover output has entries like the following
[28] "H-00212800013f1346"[2](212800013f1348) # "<COMPUTE NODE> HCA-1" lid 62 4xQDR
Ideally the correct entry in ibnetdiscover should be like the following. In the previous output IP address is missing.
[12] "H-00212800013f22d6"[1](212800013f22d7) # "<COMPUTE_NODE> S <IP> HCA-1" lid 44 4xQDR
Changes
A software upgrade.
Cause
To view full details, sign in with your My Oracle Support account. |
|
Don't have a My Oracle Support account? Click to get started! |